Key features
Through bore. Bore Dimension full 80mm diameter with outlet removed
Exceeds flow requirements: Min flow 2000 l/min @1.7 Bar (Kv=92): specified in BSEN14339 Actual flow: Kv= 157
Fully maintainable in situ
Ductile iron construction
Universal drilled inlet flange BS EN 1092:PN10/16, BS 10 Table D/E
Patent Pending
Stem drive – Stem cap in accordance with BS 750/ BS 5163-2
Ductile iron coated with WRAS approved epoxy coating Blue RAL 5017, to 250 microns min, Holiday free in accordance with WIS 04-52-01
Type 2c. Screwed down type with screwed 2½ inch round thread outlet
Autofrost valve as standard
Downloads
Specifications (.pdf)
Service Conditions
Maximum Working Pressure: 16 Bar
Temperature Range: -10°C to +70°C
Insulation essential for temperatures of 0°C and below
Standards
BSI Kite marked to BS 750:2012
Complies with Annex ZA of BS EN 14339 in respect of Construction Products Directive (CPR)
WRAS approved (materials only)
Outlet connectors – BS 336 to UK
For potable water systems EN 1074-6:2004
Corrosion resistant construction and relevant components coated in accordance with WIS-4-52-01
BS EN 1074 – 6 for disinfection products
Test/Approvals
Hydraulic test to BS 750 Seat: 1.1 x PN. Body: 1.5 x PN. Operating torque test
Resistance to operating load – MOT – 105NM – MST – 210NM
Draining – Volume of retained water 12ml after 4 minutes
Hydraulic characteristics – Kv = 92 minimum 2000 l/min @ 1.7 Bar