Pump Characteristics
The main pump supplies the flow and pressure required by the system and must be capable of driving at least 140% of the nominal flow at a pressure not below 70% of the nominal pressure.
Main pump with electric motor, bench top centrifugal pump according to DIN 24.255 with cast iron single impeller, IP55 motor and F class insulation.
Main pump with diesel motor, bench top centrifugal pump with cast iron single impeller, works within NA curve, double set of batteries for independent manual or automatic starting and a diesel tank with minimum six hours running.
Jockey (auxiliary) pump with electric motor, multicellular vertical or horizontal pump, keeps lines pressurised and compensates for possible leaks that may stop main pump from starting.
Ready to Commission
Saci fire fighting boosters feature a compact and robust design and come totally prepared and wired for commissioning at their destination.
Installation is easy and the units require minimal preventative maintenance.
Construction is in folded plate with a minimum thickness of 5mm for smaller units and laminate profile for larger units.
The drive collector is sized for a maximum water speed of 3 m/s, all non-return, close and safety valves and pressure gauges are high quality and comply to EN-12845 standards.